Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0123-00535
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2026 Commercial Building Standard APPROVED
01/15/2026 Commercial Electrical Standard APPROVED
02/05/2026 Site Zoning Standard APPROVED
02/03/2026 Water - PDSD Standard APPROVED
01/15/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
02/03/2026 Site Engineering Standard NOT REQUIRED
02/05/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/03/2026 Commercial Mechanical Standard REQUIRES RESUBMIT Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, 504.4 and, 504.6, IMC 2018.
02/03/2026 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Provide specifications for the treat sink, P3. Reference: Sections 303.4 and 402, IPC 2018.
2. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. clothes washers). Reference: Section 604.9, IPC 2018.
3. Specify the proposed sump pump and provide a detail of the installation of the sump pump, including the check valve, shut-off valve and the connection to the 2” gravity drain. Reference: Sections 712.1 through 712.3, IPC 2018.
4. Clarify how and where the new 2” gravity drain connects to the existing building drain. Reference: Section 712.3.5, IPC 2018.
02/05/2026 Fire New Construction Standard REVIEW COMPLETED
01/15/2026 PDSD Application Completeness Express REVIEW COMPLETED