Permit Number: TC-COM-0123-00507
Parcel: 111041550

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0123-00507
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2023 Site Zoning APPROVED
03/07/2023 Site Engineering NOT REQUIRED
03/08/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/21/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0123-00507

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
Elevation views not submitted.


BUILDING REVIEW COMMENTS:
Denied
Elevation views not submitted.
Need the energy code compliance report.
The bedroom windows do not meet the requirements for egress windows. A sliding window with a rough opening of only 36" wide would provide a clear opening of only 16" wide - minimum 20" is required.
Occupancy calculations should be 1 person per 200 sf of gross area (per definition).
Verify that the ventilation and lighting requirements of Chapter 12 are met.


MECHANICAL REVIEW COMMENTS:
Denied
Elevation views not submitted.
Need the energy code compliance report.
The bedroom windows do not meet the requirements for egress windows. A sliding window with a rough opening of only 36" wide would provide a clear opening of only 16" wide - minimum 20" is required.
Occupancy calculations should be 1 person per 200 sf of gross area (per definition).
Verify that the ventilation and lighting requirements of Chapter 12 are met.


ELECTRICAL REVIEW COMMENTS
Denied
Need the energy code compliance report.
The water heater is shown on the plumbing plans as being 208V but the building service is 120/240V.
Show tamper resistant receptacle details on electrical plans.
Show the subpanel feeder sizes.


PLUMBING REVIEW COMMENTS:
DeniedThe water heater is shown on the plumbing plans as being 208V but the building service is 120/240V.
Include sprinkler details, backflow preventers, etc. in plumbing drawings.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/08/2023 Fire New Construction REVIEW COMPLETED
02/08/2023 PDSD Application Completeness Express REVIEW COMPLETED