Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0123-00496
Parcel: 13109234A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0123-00496
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/23/2023 Commercial Electrical REQUIRES RESUBMIT Please indicate in detail what electrical repairs were performed. If modifications or upgrades were made to the electrical service or distribution downstream, provide a complete electrical line diagram, showing the modifications or replaced equipment. Provide sealed electrical plans stamped by an Electrical Registrant registered in the State of Arizona if design and calculations were required in order to bring the building electrical up to Code.
Any exterior lighting modifications or replacement will require compliance with the 2012 City of Tucson Outdoor Lighting Code.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson Outdoor Lighting Code, City of Tucson Commercial Plan/Permit Submittal Requirements.
02/06/2023 PDSD Application Completeness Express REVIEW COMPLETED