Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0123-00482
Parcel: 115072700

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0123-00482
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2023 Commercial Building NOT REQUIRED
02/22/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/22/2023 Commercial Electrical REQUIRES RESUBMIT 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide complete electrical plans indicating the complete scope of work in detail, sealed by an Arizona Registrant.

2. Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.

Provide site lighting plans with the following information on the plans;

(a) Provide a complete luminaire schedule.

(b) Size of the parcel in acres.

(c) See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing.

(d) 402.1 (light source color temperature requirements), shielding requirements, etc .

(e) Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1.

(f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

(g) Specify any exceptions used.

(h) Curfew lighting controls If applicable.

Do not confuse the Outdoor Lighting Code with the IECC.



Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code (OLC).
01/19/2023 PDSD Application Completeness Express REVIEW COMPLETED