Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0123-00476
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/26/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/26/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please indicate the electrical service secondary conductor sizes and types on the line diagram and verify Grounding Electrode conductor size is adequate per NEC 250.66. Provide an electrical floor plan showing all equipment and devices connected to the new Panel ‘R’. Ref; 2018 IBC section 107.2, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
| 01/17/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |