Permit Number: TC-COM-0123-00471
Parcel: 13002003B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0123-00471
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
03/27/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0123-00471

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1) Need the total area of the entire building covered fire area. The maximum allowed area for a type IIIB unseparated building without sprinklers is 12,500 sf. Sprinklers may need to be installed. Include allowed vs actual building area and height.


BUILDING REVIEW COMMENTS:
Denied
1) Need the means of egress lighting, emergency lighting, exit signs, etc. and any other specific building, electric, mechanical, and plumbing details regarding the new use of the building - show as new or existing. The building shell applied for under a separate permit would not have been approved for the requirements for this specific use of the space.
2) Need the total area of the entire building covered fire area. The maximum allowed area for a type IIIB unseparated building without sprinklers is 12,500 sf. Sprinklers may need to be installed. Include allowed vs actual building area and height.


MECHANICAL REVIEW COMMENTS:
Denied
1) Need the means of egress lighting, emergency lighting, exit signs, etc. and any other specific building, electric, mechanical, and plumbing details regarding the new use of the building - show as new or existing. The building shell applied for under a separate permit would not have been approved for the requirements for this specific use of the space.


ELECTRICAL REVIEW COMMENTS
Denied
1) Need the means of egress lighting, emergency lighting, exit signs, etc. and any other specific building, electric, mechanical, and plumbing details regarding the new use of the building - show as new or existing. The building shell applied for under a separate permit would not have been approved for the requirements for this specific use of the space.


PLUMBING REVIEW COMMENTS:
Denied
1) Need the means of egress lighting, emergency lighting, exit signs, etc. and any other specific building, electric, mechanical, and plumbing details regarding the new use of the building - show as new or existing. The building shell applied for under a separate permit would not have been approved for the requirements for this specific use of the space.
2) Need the total area of the entire building covered fire area. The maximum allowed area for a type IIIB unseparated building without sprinklers is 12,500 sf. Sprinklers may need to be installed. Include allowed vs actual building area and height.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/30/2023 Fire New Construction REQUIRES RESUBMIT Address SAFEBuilt comments.
Questions: Patricia Shelton, Patricia.Shelton@tucsonaz.gov
03/24/2023 PDSD Application Completeness REVIEW COMPLETED