01/25/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/25/2023 | Commercial Electrical | REQUIRES RESUBMIT | 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical site, power and lighting plans sealed by an Arizona Registrant. Include the locations, and types of all electrical services and or pedestals utilized for temporary power and lighting for the venders/tents set up. Provide evidence on the plans that all temporary wiring complies with 2017 NEC articles 525 and 590, 2018 IBC section 108.3, and the 2012 Tucson/Pima County Outdoor Lighting Code. Provide a copy of the Electrical Site Plan to be posted in the street fair/event office for reference if needed by first responders. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements | ||
01/17/2023 | PDSD Application Completeness | REVIEW COMPLETED |