Permit Number: TC-COM-0123-00462
Parcel: 116210220

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0123-00462
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/23/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0123-00462

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
Denied
1. Sheet TS: The occupant load for the tap room is calculated incorrectly. It appears that there is fixed seating (booths or benches) present and should be calculated appropriately. Provide a corrected occupant land in accordance with Section 1004.6.
2. At least 5% of the dining surfaces including that bar are required to have mobility features. Provide calculations of the required amount of accessible seating and indicate the locations. Additionally, ensure that surfaces are properly dispersed throughout the structure. Section 226.1 and 226.2 of the 2010 ADAAG.


MECHANICAL REVIEW COMMENTS:
Denied
1. Provide a detailed kitchen equipment schedule.
2. Provide all manufacturer specifications for the pizza oven for review.
3. Provide the reference food service drawings.


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review: BLDG #1
1). Ice Machine & Condensate piping on plan page P1.0 can't discharge to the grease system. Update illustrations & update note#13 -IPC 1003.2
2). Show roof drain conductor sizes on plan page P1.0. -IPC 1106.2 (only shows roof drain sizes)
3). This occupancy type & load requires separate mens & womens restrooms, update all affected pages' -IPC 403.2
4). Plan page P1.0 Detail #1 states water & Gas plan, no gas system is shown? -IFGC 106.3.1
5). Add fixture spacing measurements for the lavs & toilets on plan page A4.2 -IPC 404.2, 405.3.1
6). Rest room floor drains on plan page P1.0 need trap primers - IPC 1002.4.1
7). The 80 gallon water heater next to the toilet on plan page P1.0 encroaches the required fixture spacing - IPC 404.2, 405.3.1
8). The 80 gallon water heater next to the toilet on plan page P1.0 needs its relief valve piped to the exterior. -IPC 504.6 #5, #6


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/02/2023 Historic REQUIRES RESUBMIT Property is listed as a contributing resource to the Menlo Park National Register Historic District constructed in ca. 1925. Since some demolition is proposed please complete the Historic Demolition Documentation form (https://www.tucsonaz.gov/files/pdsd/Preservation/Historic_Demolition_Application_Form.pdf) and provide Full Documentation as noted.
03/23/2023 Site Engineering REQUIRES RESUBMIT See zoning comment
03/22/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0123-00462
1000 W Congress St. – C-1 (1st Review)

TRANSMITTAL: March 22, 2023, 2023
This site is located in C-1 zone (UDC 4.7.20). Food Service is a permitted use in the zone, (Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 & 5 and 4.9.13.O.

1. Zoning has reviewed the plan for compliance with development package (DP) TD-DEV-1222-00074 but until the DP has been approved by all review agencies Zoning cannot approve this plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
03/22/2023 Fire New Construction REVIEW COMPLETED
03/01/2023 PDSD Application Completeness Express REVIEW COMPLETED