Permit Number: TC-COM-0123-00459
Parcel: 141185730

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0123-00459
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2023 External Reviewers - SAFEBuilt APPROVED Activity Number: TC-COM-0123-00459

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
N/A


BUILDING REVIEW COMMENTS:
N/A


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
39 PHASE 1 - SITE LIGHTING & POWER PLAN: Comment only, consecutive circuits are typically even or odd and not sequential i.e. Panel#: 1, 3 vs you are using sequential 1, 2. Your current arrangement is awkward to wire and does not allow shared neutral or for 208V if needed for future modification. This comment also applies to Sheet #40, Phase 2. Design is code compliant and it is a suggestion only that you consult with an Electrician and revise circuits before issuing for construction. Revising Circuits as suggested will not require a revision submittal.


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/22/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
02/24/2023 Site Engineering REQUIRES RESUBMIT See Zoning Comment
02/22/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0123-00459
9683 E Rita Commerce Dr – I-1 (1st Review)

TRANSMITTAL: February 22, 2023
This site is located in I-1 zone (UDC 4.7.29)

1. Zoning has reviewed the plan for compliance with development package (DP) TD-DEV-1222-00077 but until the DP has been approved by all review agencies Zoning cannot approve this plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
02/16/2023 Fire New Construction REVIEW COMPLETED
01/28/2023 PDSD Application Completeness REVIEW COMPLETED