Permit Number: TC-COM-0123-00435
Parcel: 11717003A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0123-00435
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/05/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0123-00435

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Denied
1) The plumbing fixture calculations shown on page G1 are not correct. The details of Table 408.1 require 2 water closets for each gender when the occupancy is greater than 75 (76-150) for each gender. Correct all affected pages. Please submit the approval from the appeals process for an alternate approved design if not making changes to the plans.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/14/2023 PDSD Application Completeness Express REVIEW COMPLETED