Permit Number: TC-COM-0123-00428
Parcel: 10511061R

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0123-00428
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
03/13/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0123-00428

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
Denied
1) Still need to show the correct construction type. Type II-N is not a listed type in Table 601. Also "Non-Sales" is not a listed occupancy use in Table 1004.5 - correctly show the occupancy use groups of all areas.
2) Correctly show the allowed vs actual area (use Section 506 and Table 506.2), number of stories (use Table 504.4), and height (use Section 504 and Table 504.3).
3) Still need to show the full means of egress travel distance (through the corridor) and any new or existing exit signs meeting the requirements of section 1013 and emergency lights including the exit discharge lights meeting the requirements of section 1008 for the means of egress path through the corridor.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E2.10: May want to update General Note E with specific height requirements.


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/03/2023 PDSD Application Completeness REVIEW COMPLETED