Permit Number: TC-COM-0123-00428
Parcel: 10511061R

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0123-00428
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2023 Site Zoning APPROVED Please note that the removal of the exterior shade canopies requires a separate demolition permit.
02/13/2023 Site Engineering NOT REQUIRED
02/13/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
02/11/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0123-00428

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
Denied
INCLUDE THE ALLOWED AND ACTUAL AREA, HEIGHT, AND STORY CALCULATIONS
SHOW CORRECT CONSTRUCTION TYPE.
SHOW THE FULL MEANS OF EGRESS TRAVEL DISTANCE TO THE BUILDING EXIT.
INCLUDE THE NEW AND EXISTING EXIT SIGNS AND EMERGENCY LIGHTING MEETING THE REQUIREMENTS OF SECTION 1008 INCLUDING THE EXIT DISCHARGE LIGHTING.
DETAIL FIRE-RATED WALL ASSEMBLIES AND THE USES OF THE ADJACENT SPACES FOR POSSIBLE SEPARATION.
SHOW ACCESSIBLE DRESSING ROOMS MEETING THE DETAILS OF SECTION 803 AND THE DOOR SWING REQUIREMENTS OF SECTION 803.3
SHOW THE ACCESSIBLE ROUTE FROM THE ADA PARKING SPACES TO THE ENTRANCES.
PENDING THE RESULTS OF THE PLUMBING AND OTHER REVIEWS.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E2.10: May want to update General Note E with specific height requirements


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
01/30/2023 Fire New Construction REVIEW COMPLETED
01/25/2023 PDSD Application Completeness REVIEW COMPLETED