Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0123-00416
Parcel: 140400650

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0123-00416
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
01/10/2023 Commercial Electrical REQUIRES RESUBMIT 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by an Arizona Registrant.

2. Provide 2 ground rods 6 feet or more apart or verify 25 ohms ground resistance or less to earth for a single rod, NEC 250.53(A) (2) Exception.

3. Show all electrical services and locations on the property or building(s) on the electrical site plan. If more than one electrical service, then verify compliance with NEC 230.2 if applicable.

Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
02/01/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-COM-0123-00416
7201 S COMSTOCK RD Zoning I-1

TRANSMITTAL DATE:ā€ˇFebruary 1, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Please clarify the proposed use of the electrical service, An electrical service will require a principal use/structure.


If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
01/06/2023 PDSD Application Completeness REVIEW COMPLETED