Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2023 Commercial Electrical APPROVED
05/16/2023 Commercial Mechanical APPROVED The specified water-source heat pumps have a hanging weight of 203 pounds. Structural calculations and connection details are required but not shown. The mechanical details are inadequate for showing the connection to the building structure. Reference: Section 302.1, IMC 2018.
05/16/2023 Commercial Plumbing APPROVED Correct the plumbing fixture calculations. The occupancy type is Business, not Mercantile. For Business occupancy, 2 lavatories are required for 48 occupants. The calculations need to include the occupants of the rest of the 2nd floor.
05/12/2023 Commercial Structural APPROVED
05/16/2023 Bldg Permits - Post Review REVIEW COMPLETED