Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.4
Permit Number - TC-COM-0123-00414
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/02/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/02/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Activity Number: TC-COM-0123-00414 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1) Submit the spec sheet for the heat pumps. This is needed to determine the weight, piping, and electrical requirements of the units. 2) Details for the connection and reinforcement of the structure for the support of the weight of the HVAC equipment not submitted. Page M3.0 does not show these details. BUILDING REVIEW COMMENTS: Denied 1) The occupant load calculations shown on page G1 are to include the 1 person per 15 sf or 1 occupant per 7 ft for chairs only for the areas with tables and chair seating for the cafe, conference rooms, training rooms, reception area, and similar areas as detailed in Table 1004.5. 2) Submit the spec sheet for the heat pumps. This is needed to determine the weight, piping, and electrical requirements of the units. 3) Details for the connection and reinforcement of the structure for the support of the weight of the HVAC equipment not submitted. Page M3.0 does not show these details. 4) Include the correct plumbing fixture calculations on page G1 based on the correct occupant load. Table 403.1 requires 1 water closet for each male and female toilet room for 1 to 25 occupants and 2 water closets for 26 to 50 occupants. An additional 1 water closet is required for every 50 occupants after the first 50 of each gender. Lavatories are 1 in each toilet room for the first 40 occupants and a second lavatory for 41 to 80 occupants of each gender. The existing toilet rooms do not meet the minimum requirements of the occupant load of this space alone and are shared with other spaces. Accessible drinking fountains are required for each 100 occupants - include drinking water details. 5) The toilet rooms do not meet the accessibility requirements of ICC A117.1 section 603 and the requirements of IEBC sections 305.4, 305.7, 30.5.8.10 apply to the accessible route, toilet rooms, etc. for the change of use and alteration of this space. 6) Show the accessible route and signage. 7) Show the existing (or new) emergency lights for the means of egress stairs as required in section 1008. The electrical panel schedules need to include the correct labeling for the new spaces and circuits per NEC sections 110.22 and 408.4. The lighting circuits are not shown. MECHANICAL REVIEW COMMENTS: Denied 1) Submit the spec sheet for the heat pumps. This is needed to determine the weight, piping, and electrical requirements of the units. 2) Details for the connection and reinforcement of the structure for the support of the weight of the HVAC equipment not submitted. Page M3.0 does not show these details. ELECTRICAL REVIEW COMMENTS: Denied 1) Submit the spec sheet for the heat pumps. This is needed to determine the weight, piping, and electrical requirements of the units. 2) Show the existing (or new) emergency lights for the means of egress stairs as required in section 1008. The electrical panel schedules need to include the correct labeling for the new spaces and circuits per NEC sections 110.22 and 408.4. The lighting circuits are not shown. PLLUMBING REVIEW COMMENTS: Denied 1) The occupant load calculations shown on page G1 are to include the 1 person per 15 sf or 1 occupant per 7 ft for chairs only for the areas with tables and chair seating for the cafe, conference rooms, training rooms, reception area, and similar areas as detailed in Table 1004.5. 2) Include the correct plumbing fixture calculations on page G1 based on the correct occupant load. Table 403.1 requires 1 water closet for each male and female toilet room for 1 to 25 occupants and 2 water closets for 26 to 50 occupants. An additional 1 water closet is required for every 50 occupants after the first 50 of each gender. Lavatories are 1 in each toilet room for the first 40 occupants and a second lavatory for 41 to 80 occupants of each gender. The existing toilet rooms do not meet the minimum requirements of the occupant load of this space alone and are shared with other spaces. Accessible drinking fountains are required for each 100 occupants - include drinking water details. 3) The toilet rooms do not meet the accessibility requirements of ICC A117.1 section 603 and the requirements of IEBC sections 305.4, 305.7, 30.5.8.10 apply to the accessible route, toilet rooms, etc. for the change of use and alteration of this space. 4) Show the accessible route and signaged If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
04/20/2023 | PDSD Application Completeness | REVIEW COMPLETED |