Permit Number: TC-COM-0123-00399
Parcel: 12108001B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0123-00399
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2023 Site Engineering APPROVED
11/03/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
10/17/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. Plan sheet ‘CD03’ makes reference in the details, "Conduit per Electrical”.

Provide complete electrical plans showing all power and lighting wiring methods, not just ‘Low Voltage’ . Provide complete compliance with 2017 NEC, 2012 City of Tucson Outdoor Lighting Code where applicable.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code.
10/04/2023 PDSD Application Completeness REVIEW COMPLETED
11/03/2023 Signs REVIEW COMPLETED RE: sign relocation review only
For: menu boards / clearance bar / access point signs
AT: Starbucks / 6291 E Speedway Bl
Permit: TC-COM-0123-00399
Date: 11/3/23
Reviewer: H.Thrall (Heather.Thrall@tucsonaz.gov)

Code: Unified Development Code 7.4. - maintain 1' distance from face of drive thru curb to leading edge of sign or clearance bar support.

Note - state law requires the sign contractor submit a separate sign permit for review of all construction aspects for the signs (electrical - volts, amps, circuits, shut off, Outdoor Lighting Code aspects: dimming capabilities, 4400k max at day 200 Nits at sunset, shut off at midnight with timer, and all footer and anchor supports).

Staff fully acknowledges that the G.C. will auger and pour in collaboration with the sign contractor.

Staff was unable to review the supports for the signs herein, as no specific anchor schedule is provided with the footer schedule.

Provide to the sign contractor (Marana Signs / T22OT00248) the plan set, show the anchor schedule with the corresponding footer schedule and seal your updated diagrams.

No canopy station is to be installed here. Note that specific engineering is required for the order canopy station, with detailed calculations due to size and cantilevered roofing system.

You may reach me at Heather.Thrall@tucsonaz.gov or at 520-837-4961 if you have any questions. I'm available to guide / assist as needed. Otherwise, sign contractor will process. Thank you.
11/01/2023 Site Zoning REVIEW COMPLETED