Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0123-00399
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/23/2023 | Site Engineering | APPROVED | |||
11/03/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/17/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Plan sheet ‘CD03’ makes reference in the details, "Conduit per Electrical”. Provide complete electrical plans showing all power and lighting wiring methods, not just ‘Low Voltage’ . Provide complete compliance with 2017 NEC, 2012 City of Tucson Outdoor Lighting Code where applicable. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code. |
||
10/04/2023 | PDSD Application Completeness | REVIEW COMPLETED | |||
11/03/2023 | Signs | REVIEW COMPLETED | RE: sign relocation review only For: menu boards / clearance bar / access point signs AT: Starbucks / 6291 E Speedway Bl Permit: TC-COM-0123-00399 Date: 11/3/23 Reviewer: H.Thrall (Heather.Thrall@tucsonaz.gov) Code: Unified Development Code 7.4. - maintain 1' distance from face of drive thru curb to leading edge of sign or clearance bar support. Note - state law requires the sign contractor submit a separate sign permit for review of all construction aspects for the signs (electrical - volts, amps, circuits, shut off, Outdoor Lighting Code aspects: dimming capabilities, 4400k max at day 200 Nits at sunset, shut off at midnight with timer, and all footer and anchor supports). Staff fully acknowledges that the G.C. will auger and pour in collaboration with the sign contractor. Staff was unable to review the supports for the signs herein, as no specific anchor schedule is provided with the footer schedule. Provide to the sign contractor (Marana Signs / T22OT00248) the plan set, show the anchor schedule with the corresponding footer schedule and seal your updated diagrams. No canopy station is to be installed here. Note that specific engineering is required for the order canopy station, with detailed calculations due to size and cantilevered roofing system. You may reach me at Heather.Thrall@tucsonaz.gov or at 520-837-4961 if you have any questions. I'm available to guide / assist as needed. Otherwise, sign contractor will process. Thank you. |
||
11/01/2023 | Site Zoning | REVIEW COMPLETED |