Plan Number: TC-BCA-1224-00051
Parcel: 124050620

Review Status: Approved

Review Details: BUILDING OFFICIAL APPEAL REVIEW v.1

Plan Number - TC-BCA-1224-00051
Review Name: BUILDING OFFICIAL APPEAL REVIEW v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
Building Official APPROVED
Residential Building NOT REQUIRED
Bldg Permits - Post Review REVIEW COMPLETED
Commercial Building REVIEW COMPLETED ADDED NOTE: This project also requires an appeal for openings in rated exterior wall less than 10 feet from the property line.
The following is the result of research conducted by Mark Masek for Juan Garcia related to this appeal. Juan Garcia will be the final say in this matter. This request should be approved based as it appears the intent of the code is being met.
Exterior Exit Stairways
1. The exterior exit stairway with a fire separation distance of less than 10 feet appears to meet the intent of the code as follows.
A. The current use of the adjacent site next to the exterior stairway is a parking lot with only horizontal construction.
B. If the adjacent structure expanded and is within 10 feet of the property line, by code it will be a 1-hour fire resistive rated wall. This will meet the fire separation distance requirements for the proposed exterior stairway.