Plan Number: TC-BCA-1125-00035
Parcel: 117082340

Address:
934 S 6TH AV

Review Status: Approved

Review Details: BUILDING OFFICIAL APPEAL REVIEW v.1

Plan Number - TC-BCA-1125-00035
Review Name: BUILDING OFFICIAL APPEAL REVIEW v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
Bldg Permits - Post Review Express REVIEW COMPLETED
Building Official Fast REVIEW COMPLETED See Commercial Building Review
Commercial Building Express REVIEW COMPLETED Note: The following research and recommendations are provided for informational purposes only and do not constitute a decision on the outcome of this appeal. The Building Official will make the final determination.
The use of the space as a single-bay golf simulator room is a unique condition; however, the proposed occupant load of one person appears understated. IBC Table 1004.5 lists a similar use—bowling lanes—with an occupant load factor of 5 occupants per lane. Please revise the occupant load for the Golf Simulator Room to 5 occupants in alignment with this comparable use. Please update the number of occupants to 5, matching the similar use in IBC Table 1004.5 for Bowling Center Lanes of 5 occupants per lane as the Occupant Load Factor and resubmit all documents.

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov