Review Details: BUILDING OFFICIAL APPEAL REVIEW v.1
Plan Number - TC-BCA-1125-00035
Review Name: BUILDING OFFICIAL APPEAL REVIEW v.1
Review Status: Approved
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| Bldg Permits - Post Review Express | REVIEW COMPLETED | ||||
| Building Official Fast | REVIEW COMPLETED | See Commercial Building Review | |||
| Commercial Building Express | REVIEW COMPLETED | Note: The following research and recommendations are provided for informational purposes only and do not constitute a decision on the outcome of this appeal. The Building Official will make the final determination. The use of the space as a single-bay golf simulator room is a unique condition; however, the proposed occupant load of one person appears understated. IBC Table 1004.5 lists a similar use—bowling lanes—with an occupant load factor of 5 occupants per lane. Please revise the occupant load for the Golf Simulator Room to 5 occupants in alignment with this comparable use. Please update the number of occupants to 5, matching the similar use in IBC Table 1004.5 for Bowling Center Lanes of 5 occupants per lane as the Occupant Load Factor and resubmit all documents. Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |