Plan Number: TC-BCA-1025-00032
Parcel: 10818003B

Review Status: Approved

Review Details: BUILDING OFFICIAL APPEAL REVIEW v.1

Plan Number - TC-BCA-1025-00032
Review Name: BUILDING OFFICIAL APPEAL REVIEW v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
Building Official Fast APPROVED
Bldg Permits - Post Review Express REVIEW COMPLETED
Commercial Building Express REVIEW COMPLETED Note: The following research and recommendations are provided for informational purposes only and do not constitute a decision on the outcome of this appeal. The Building Official will make the final determination.
Based on review, the proposed occupant load appears reasonable and, when applying IBC Table 1004.5, is close to the tabular Occupant Load Factors either way the occupant load is calculated only one door is required, as follows:
• Exercise Area: 1,150 sq. ft. ÷ 50 sq. ft. per person = 23 occupants
• Lobby: 308 sq. ft. ÷ 15 sq. ft. per person = 20 occupants
Less than 50 occupants, only one exit is required.
The Total Occupant Load of 37 is reasonable
The primary issue pertains to the number of required water closets. Per IBC Section 2902, a Group B occupancy of this size would typically require two water closets. However, given the nature of the use—primarily serving staff and only an occasional customer—the existing single-user water closet appears to be more than adequate for the intended occupancy and use of the space.