Plan Number: TC-BCA-0726-00115
Parcel: 13205015H

Address:
3430 E 36TH ST

Review Status: Approved

Review Details: BUILDING OFFICIAL APPEAL REVIEW v.1

Plan Number - TC-BCA-0726-00115
Review Name: BUILDING OFFICIAL APPEAL REVIEW v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
Building Official Fast APPROVED
Bldg Permits - Post Review Express REVIEW COMPLETED
Commercial Building Express REVIEW COMPLETED Note: The following research and recommendations are provided for informational purposes only and do not constitute a decision on the outcome of this appeal. The Building Official will make the final determination.

Based on a cursory review, modern brick manufacturing facilities of this size typically employ approximately 85–105 workers per shift. Accordingly, the proposed operational occupant load of 100 persons appears reasonable. The proposed restroom facilities would accommodate up to 400 occupants.

Two approaches may be considered:
• Reduce the approved F-2 occupant load to the requested 100 persons, thereby reducing the required plumbing fixtures accordingly.

• Maintain the calculated F-2 occupant load of 1,270 to ensure the building's means of egress is evaluated for the maximum code occupant load, while granting an appeal to reduce the required plumbing fixtures based on the proposed operational occupancy.

If the applicant provides sufficient evidence demonstrating that the facility will be operationally limited to 100 occupants, approval of the reduced occupant load may be appropriate. This determination is within the Building Official's discretion, provided it is consistent with the adopted codes and the building otherwise complies with all applicable code requirements.