Review Details: BUILDING OFFICIAL APPEAL REVIEW v.1
Plan Number - TC-BCA-0426-00079
Review Name: BUILDING OFFICIAL APPEAL REVIEW v.1
Review Status: In Review
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| Bldg Permits - Post Review Express | PENDING ASSIGNMENT | ||||
| Building Official Fast | PENDING ASSIGNMENT | ||||
| Commercial Building Express | REVIEW COMPLETED | TC-BCA-0426-00079 410 N TOOLE AV Unit:116 Note: The following research and recommendations are provided for informational purposes only and do not constitute a decision on the outcome of this appeal. The Building Official will make the final determination. Since the rinse area is being added as part of this project, at least one accessible rinse fixture is required to comply with IBC Section 1110.2. This may be provided as either a roll-in shower or a transfer-type shower designed in accordance with 2017 ICC A117.1 Section 608. The accessible rinse fixture must include all applicable features, including but not limited to a seat, grab bars, operable controls, and a hand-held shower. Based on this review, it appears the proposed rinse area is required to be accessible. |