Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Plan Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING OFFICIAL APPEAL REVIEW v.1
Plan Number - TC-BCA-0425-00021
Review Name: BUILDING OFFICIAL APPEAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| Bldg Permits - Post Review Express | PENDING ASSIGNMENT | ||||
| Building Official Fast | REQUIRES RESUBMIT | Appeal not approvable at this time. See Commercial Building review comments. | |||
| Commercial Building Express | REVIEW COMPLETED | 1. The following is my research and recommendation as the Building Official will make the final decision. Since the Art Room is specifically required to provide exhaust at a rate of 0.7 CFM/SQFT because these spaces often generate airborne contaminants like dust, fumes, vapors, and odors from various artistic processes. These contaminants can be harmful to health and create an undesirable indoor environment. Exhaust systems remove these contaminants, ensuring a healthier and more comfortable environment for the occupants. Even those it is stated the instructor would only use non-toxic art materials; a code compliant exhaust system would ensure acceptable indoor air quality in all instances. Based on this information the appeal, as presented, does not appear to meet the intent of the code. Approval is not recommended in this case. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |