Plan Review Detail
Review Status: Approved
Review Details: BUILDING OFFICIAL APPEAL REVIEW v.2
Plan Number - TC-BCA-0325-00014
Review Name: BUILDING OFFICIAL APPEAL REVIEW v.2
Review Status: Approved
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| Building Official Fast | NOT REQUIRED | Equipment re-location resolved. See Residential Building review comment. | |||
| Residential Building Express | NOT REQUIRED | TC-BCA-0325-00014 (6774 E CALLE LUNA TUCSON, AZ 85710) 1. PV equipment, including the DG Disconnect, has been relocated to the same location as the main service entrance. There appears to be NO need for this appeal any longer. If there is no appeal required, then please withdraw this BCA permit. 2. Verify interconnection method at the main panel and provide appropriate warning labels as required by NEC 705.12(B)(2)(3)(C). The panel schedule for the main service panel shows 180A of connected overcurrent protection devices and would not meet this interconnection method. 3. Resubmit updated plans to the Solar permit, TC-RES-0225-00917. |
|||
| Bldg Permits - Post Review Express | REVIEW COMPLETED |