Review Status: Approved

Review Details: BUILDING OFFICIAL APPEAL REVIEW v.1

Plan Number - TC-BCA-0226-00010
Review Name: BUILDING OFFICIAL APPEAL REVIEW v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
Building Official Fast APPROVED
Residential Building Express NOT REQUIRED
Bldg Permits - Post Review Express REVIEW COMPLETED
Commercial Building Express REVIEW COMPLETED Note: The following research and recommendations are provided for informational purposes only and do not constitute a decision on the outcome of this appeal. The Building Official will make the final determination. Based on review, the proposed occupant load appears reasonable and, when applying IBC Table 1004.5, is equal to the tabular Occupant Load, and only one door is required, as follows: Exercise Area: 1,064 sq. ft. ÷ 50 sq. ft. per person = 22 occupants • Lobby: 287 sq. ft. ÷ 15 sq. ft. per person = 20 occupants. Private workout and locker room 263 sf 6 occupants equals 48. Less than 50 occupants, only one exit is required.

The primary issue pertains to the number of required water closets. Per IBC Section 2902, a Group B occupancy of this size would typically require two water closets.

However, given the nature of the use—primarily serving staff and only an occasional customer—the existing single-user water closet appears to be more than adequate for the intended occupancy and use of the space.