Plan Number: T22PRE0249
Parcel: 132130260

Address:
1501 E METRIC PL

Review Status: Approved

Review Details: PRE-APPLICATION CONFERENCE REVIEW v.1

Plan Number - T22PRE0249
Review Name: PRE-APPLICATION CONFERENCE REVIEW v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
Fire New Construction REVIEW COMPLETED F.D.C. shall face the street side of the building, IFC 2018, Chapter 9, Section 912, 912.2.1 and shall not be obstructed by a gate
Fire hydrants shall be located within 400 ft of new structures. IFC 2018, Chapter 5, Section 507.5.1 and also in accordance with IFC Appendix D. Please show new and existing fire hydrant locations on the plans and or fire sprinklers shall be installed.
Questions:
Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
Site Engineering REVIEW COMPLETED Engineering Notes:

1. Balanced Basin Detention & First Flush Retention required
2. Drainage Report required, Storm Water Pollution Prevention Plan, DEQ Dust Control Permit required
3. Refuse calculations required & enclosures if needed.
4. Provide approval from utilities that office area encroachment into 10' utility easement is acceptable.
5. Sidewalk required along Metric Pl. & Pedestrian circulation path required to all areas. TSM 7-01.3.1 & TSM 10-01.2.7.A require all streets to have a sidewalk area on each side of the street Public or Private.
6. Curb cuts and driveways must be a minimum of 20 feet from a fire hydrant.

Joshua Garcia
joshua.garcia@tucsonaz.gov
Site Landscape REVIEW COMPLETED CDRC TRANSMITTAL

PROJECT: CITIZENS TRANSFER & STORAGE
ACTIVITY NO. T22PRE0249
ADDRESS/PARCEL: 1501 E METRIC PL/132-13-0260
ZONING: I-1

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting.

1. A NPPO is required per UDC 7.7.3-B. The NPPO is intended to encourage preservation in place of healthy native plants through sensitive site design that minimizes the disruption of areas within the site containing plants while allowing for salvage and transplantation of plants on the site that are likely to survive. A Native Plant Preservation Plan, Section 7.7.4, is required to be submitted or approved or a request for an exception from the Native Plant Preservation requirements approved in accordance with Sections 7.7.3.D.3 & .4 of the UDC and Admin. Manual Section 2-11.0.0 prior to Grading Plan approval.
2. A landscape plan is required per 7.6.2.B.1-b . The Unified Development Code (UDC) requires all new development or an expansion of greater than 25% of an existing development to submit a landscape plan, UDC 7.6.2. Preparation of the landscape plan shall adhere to UDC 7.6.4 and Administrative Manual 2-10.
3. Ensure the required number of trees is in all vehicular parking areas (1 tree: 6-8 parking spaces) per UDC 7.6.4.B.1. Placing trees along the edge of a parking area or at the ends of parking row does not meet the intent of the UDC. All spaces within 40’ of a tree is only one of the requirements. The intent is to provide as much shade on the asphalt as possible (TSM 5-01.3.2), and the requirement is 1 tree per 6-8 parking spaces; trees are expected to be placed within the parking area itself to provide shade on asphalt. Trees are to be distributed evenly throughout the parking area, UDC 7.6.4.1.B.1, UDC Technical Standards Manual 5-01-.3.2 and UDC 7.6.4.B.1.a.
4. A street landscape border as well as a 5’ screen is required on S Wall St & E Metric Pl. per UDC 7.6.4.C-2 and Table 7.6.4-1
5. One canopy tree is required every 33 linear feet in the landscape border. UDC 7.6.4C-1.a
6. Street landscape borders must be a minimum of 10’ wide as measured from the street property line. UDC 7.6.4.2.a
7. Street landscape borders must be covered with an appropriate inorganic ground cover, such as decomposed granite. UDC 7.6.4.2.d
8. 50% or more of the area of the street landscape border must be covered with shrubs or vegetative ground cover. UDC 7.6.4.e
9. All landscape plans shall incorporate water conserving design as defined in UDC Section 7.6.6, Use of Water, and as described in the Technical Standards Manual 5.01-5.11.
10. The Landscape Plan should match the Commercial Rainwater Harvesting Plan as well as the Grading Plan. Landscape Plan must have spot elevations in the detention/retention areas as well as in all water harvesting areas in the Landscape Plan.
11. A Commercial Rainwater Harvesting plan is required per UDC Technical Standards Manual – Section 4-01.3.0. and Section 5-01.0.0 Landscaping and Screening. Adherence to the Low Impact Development Standards outlined in Section 5 of the PCRFCD Design Standards for Stormwater Detention and Retention is required and shall work in conjunction with the Commercial Rainwater Harvesting design. Using Low Impact Development design and water harvesting provides critical basin detention and first flush retention for all new development and impervious area. The newly adopted Detention/Retention Manual can be found: https://webcms.pima.gov/UserFiles/Servers/Server_6/File/Government/Flood%20Control/Rules%20and%20Procedures/Stormwater%20Detention-Retention/dssdr-final-201406-manual.pdf

With CoT edits to the manual are found at: https://www.tucsonaz.gov/files/pdsd/codes/Detention_Retention_Manual_Tech_Standards_Amemdments.pdf

If you have any questions about these comments, I can be reached at Matthew.Carlton@tucsonaz.gov or 520-837-4988
Site Zoning REVIEW COMPLETED FROM: Iman Monshizadeh

PDSD Zoning Review Section

PROJECT: T22PRE0249 (Citizens Transfer and storage)

TRANSMITTAL DATE: 11/15/2022

1. A Development Package will be required for this site. Information on the development package can be found at: https://www.tucsonaz.gov/pdsd/apply-permit

2. Commercial storage is permitted in the I-1 zone. Use specific standards 4.9.10.A and 4.9.13.Q Apply. Depending on the specifics of the business conducted, the use may change.

3. Some proposed parking spaces, curbs and structures are located within the utility easement. If easements are being abandoned or removed state them as such on the submittal plan. Proposed improvements cannot be located within an easement.

4. Setbacks for Metric Pl will likely be considered using the developing area setbacks with an ADT of 14 or less. Setbacks for this ADT are as follows:

(5’ or ½ * Height of structure measured from structure to back of existing/future curb)
Or
(1’ measured from structure to property line)
The setback that is the greatest of the 3 will apply.


For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov / (520) 837-4082
Traffic Engineering Review REVIEW COMPLETED No Comments
TW Hydraulic Modeling Review REVIEW COMPLETED 1. Tucson Water’s New Area Development Unit has no objections to the proposed development.
2. The above comments are based on the limited preliminary information provided by the applicant and should not be construed as a complete review of the proposal. Any questions, comments or concerns about these comments may be directed to:

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
201 N. Stone Avenue, #2-220
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106
tim.rowe@tucsonaz.gov