Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - T22FC00453
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/16/2022 | Fire New Construction | REQUIRES RESUBMIT | Flow summary for the duct nozzle does not match the drawings. Flow summary lists a 1W while the drawings show a 2W. Make corrections. | ||
12/08/2022 | TFD Application Completeness Check | REVIEW COMPLETED |