Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - T22CM08164
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/07/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/07/2023 | Commercial Mechanical | REQUIRES RESUBMIT | Please submit your revised drawings along with a detailed response letter, which states how all Building/Mechanical Review Section comments were addressed. 1. Please amend plans to note or otherwise indicate; Provide smoke detectors in the return air duct, upstream of any outside air connections, for all air distribution systems moving than 2,000 CFM. Reference: Section 606.2.1, IMC 2018, as amended by the City of Tucson. 2. Sheet S1: Please amend Structural design Criteria to use the codes as amended and adopted by of the City of Tucson 2018 International Building Code (IBC) 2018 International Existing Building Code (IEBC) Local Amendments to Above Codes ( www.tucsonaz.gov/pdsd/building-codes ) 3. Structural Calculations: Please amend Design Criteria to reflect the 2018 International Building Code treat as atypical comment. |
||
| 12/06/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |