Permit Number: T22CM08145
Parcel: 13824101L

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM08145
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2022 Commercial Plumbing APPROVED Water review
11/01/2022 Site Zoning APPROVED
10/31/2022 Site Engineering NOT REQUIRED
12/05/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/01/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM08145

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved
Not applicable to scope of work


BUILDING REVIEW COMMENTS:
Denied
1. Sheet A1.0 (Floor Plan & Demo Plan) / Keynote #2: This keynote references wall section detail 5/A2.0. Detail 5/A2.0 does not appear on Sheet A2.0, please revise.
2. Sheet A1.0 (Floor Plan & Demo Plan) / Keynote #3: This keynote indicates the placement of a roll down shutter or door; however, the floor plan (3/A1.0) appears to indicate this roll down shutter or door at both corridors. Please clarify if this is correct.
3. Sheet A2.0 (Reflected Ceiling Plan & Details) / Detail 3/A2.0 (3 5/8” MTL Stud (6” Above Ceiling) Typ.): Please clarify if this detail is the one referenced in Keynote #2 – Sheet A1.0.
4. Sheet A3.0 (Interior Elevations & Door Schedule) / Door Schedule: Keynote #3 – Sheet A1.0 refers to the installation of a “roll down door”. Please include this roll down door within the schedule.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/01/2022 Fire New Construction REVIEW COMPLETED