Permit Number: T22CM08136
Parcel: 11201009B

Address:
2811 E ALLEN RD

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - T22CM08136
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2022 Site Zoning APPROVED
10/31/2022 Site Engineering NOT REQUIRED
10/31/2022 Site Landscape NOT REQUIRED
01/30/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
11/14/2022 Residential Building REQUIRES RESUBMIT T22CM08136
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet Zoning and other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. Provide a separate application and site plan for the pool demolition.
2. Provide a signed Confirmation of Notice of Demolition form for the demo of the 1-story dwelling, R104.
3. Approval of a new Overhead service replacing an underground line requires an Underground Service Waiver request. This is not usually approved if TEP has underground service available in the area.

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Update insulation reference notation on sheet A6.1.

PLUMBING PLANS:

1. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe and water meter size.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1505.4. Show the system and appropriate flow rate setting on the plans. A four bedroom dwelling over 3000 SF requires a 90 CFM continuous setting. Update the 75 CFM notation.
2. Show impact protection for appliances located in the garage, M1307.3.1.

ELECTRICAL PLANS:

1. Verify that the overhead electrical drop rather than an underground line meets service standards by TEP.
2. Show the location of a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace, in a utility or laundry room, N1101.14. Add notation to plans.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
01/30/2023 Fire New Construction REVIEW COMPLETED