Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM08135
Parcel: 110120990

Address:
2650 N WYATT DR

Review Status: Requires Resubmit

Review Details: RESTAMP - COMMERCIAL v.1

Permit Number - T22CM08135
Review Name: RESTAMP - COMMERCIAL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2023 Commercial Plumbing APPROVED
05/30/2023 Commercial Structural APPROVED
05/30/2023 Commercial Mechanical NOT REQUIRED
05/25/2023 Site Engineering NOT REQUIRED
05/30/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/26/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide complete electrical power and lighting floor plans showing all the electrical equipment, devices, new lighting as applicable to this project. Show designated branch circuits numbers and associated breaker panel. Correlate with the Plan Notes for the electrical equipment, plan sheet E1.01.

2 Provide complete panel schedules showing OCPD’s associated with the equipment. Verify panel capacity is adequate for the new loads. NEC art 220 and 408.

Ref; 2018 IBC section 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal Requirements.
05/25/2023 Fire New Construction REVIEW COMPLETED