Review Status: Requires Resubmit
Review Details: RESTAMP - COMMERCIAL v.1
Permit Number - T22CM08135
Review Name: RESTAMP - COMMERCIAL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/30/2023 | Commercial Plumbing | APPROVED | |||
05/30/2023 | Commercial Structural | APPROVED | |||
05/30/2023 | Commercial Mechanical | NOT REQUIRED | |||
05/25/2023 | Site Engineering | NOT REQUIRED | |||
05/30/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
05/26/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Provide complete electrical power and lighting floor plans showing all the electrical equipment, devices, new lighting as applicable to this project. Show designated branch circuits numbers and associated breaker panel. Correlate with the Plan Notes for the electrical equipment, plan sheet E1.01. 2 Provide complete panel schedules showing OCPD’s associated with the equipment. Verify panel capacity is adequate for the new loads. NEC art 220 and 408. Ref; 2018 IBC section 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal Requirements. |
||
05/25/2023 | Fire New Construction | REVIEW COMPLETED |