Permit Number: T22CM08117
Parcel: 106024110

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM08117
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2022 Commercial Electrical APPROVED
01/05/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
01/05/2023 Commercial Building REQUIRES RESUBMIT General
1) This is a commercial project and shall comply with 2018 IBC. Update reference on sheet (as.01).
12/13/2022 Commercial Mechanical REQUIRES RESUBMIT 1. The 2018 International Mechanical Code with Local Amendments and the 2018 International Energy Conservation Code (Residential Section) are the relevant codes for this project, not the 2018 IRC. Revise the Mechanical Plan Notes and the Whole House Ventilation Schedule as needed.
2. Ventilation for kitchens in private dwellings requires a minimum of 25 CFM (continuous operation while occupied) or 100 CFM (intermittent operation) of mechanical exhaust per room. Reference: Section 403.3.2.3 and exception 1, Section 505.3, IMC 2018.
12/13/2022 Commercial Plumbing REQUIRES RESUBMIT 1. The 2018 International Plumbing Code with Local Amendments and the 2018 International Energy Conservation Code (Residential Section) are the relevant codes for this project, not the 2018 IRC. Revise the Plumbing Plan Notes and the Whole House Ventilation Schedule as needed.
2. Specify that all proposed plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018.