Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM08078
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2022 Commercial Plumbing APPROVED
10/31/2022 Site Engineering APPROVED
11/02/2022 Site Zoning APPROVED
11/30/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/08/2022 Commercial Electrical REQUIRES RESUBMIT Provide complete electrical plans for the Propane Tank and dispensing system. Plans are to be prepared and sealed by an Electrical Engineer registered in the State of Arizona.

Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC 2018 IECC, City of Tucson Commercial Plan /Permit Submittal Requirements.
11/30/2022 Commercial Mechanical REQUIRES RESUBMIT 1. Show that the proposed replacement rooftop units meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018.
2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified new HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
3. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.
11/02/2022 External Reviewers - Willdan REQUIRES RESUBMIT Activity Number: T22CM08078

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


DENIED:
Sheet T1.0 Provide path of travel to the Public Way per ICC A117 and ADAAG
Sheet T1.0 How many gallons does the propane tank hold? Obtain permit form COT Fire Department.
Sheet T1.0 Provide accessible access to sales areas outside the Main Building. If POS is provide for outside sales area provide details of check out counters. per ADAAG
Sheet CS1.1 Provide occupant load of mezzanine to determine exiting. Chapter 10 IBC
Sheet A1.1 Provide expanded view of restrooms showing ADAAG Compliance.
Sheet A1.1 Provide details for POS Counters and ADAAG Access.Are there any other Check Out Areas besides the front of the store?
Sheet A1.1d Provide details for all racking, show attachment details. Show height of all racking.
Sheet A1.1d How tall are the racks in the storage area?
Sheet A1.1d Show where Gun Powder is being stored. Provide maximum Gun Powder to be on hand.
Sheet A1.3 Provide roof drain calculations verifying it complies with current requirements. Show how roof slopes to drains.
Sheet A1.3 Provide Structural Calculations for adding additional Mechanical equipment on roof. Provide weight of each new unit.
Sheet A2.1 Provide note that all door hardware with meet the requirements of ADAAG and IBC Chapter 10
Sheet S1.2 Provide occupant load for mezzanine and provide exiting plan.
Sheet S1.2 Provide Structural Calculations for new mezzanine and masonry openings.

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/28/2022 Fire New Construction REVIEW COMPLETED