Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM08065
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2022 Commercial Electrical APPROVED
12/15/2022 Commercial Plumbing APPROVED
11/25/2022 Site Engineering APPROVED
11/02/2022 Site Zoning APPROVED
12/15/2022 Commercial Mechanical NOT REQUIRED
12/15/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
11/02/2022 External Reviewers - Willdan REQUIRES RESUBMIT Activity Number: T22CM08065

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


DENIED:
Revise to 2018 IBC Chpt 11 & 2010 ADA
Provide basic code data: const type, occupancy (U), sf, etc.
All working parts to include the outlet need to be within reach ranges of ANSI 308, comply with provisions of operable parts of ANSI 309, and have a clear floor space complying with 305.
Is Kiosk in an accessible route?
Provide all 4 elevations. Provide door info 2018 IBC 107.2.1
Revise to reflect currently adopted Tucson codes: 2018 IBC
Please provide completed Tucson SIC form for Specials per 2018 IBC Chpt. 17, 107.2.1
Provide panel schedule, circuiting + ocpd sizes, load calcs. (they are not found elsewhere on plans-provide on Electrical sheet please)
Confusing/unclear: Please provide/show grounding in compliance with 2017 NEC Article 250 (min of 2 ground rods and/or 20' CU concrete encased electrode, etc.)


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/26/2022 Fire New Construction REVIEW COMPLETED