Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - T22CM08058
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/31/2022 | Site Engineering | APPROVED | |||
| 10/31/2022 | Site Landscape | APPROVED | |||
| 10/31/2022 | Site Zoning | APPROVED | |||
| 11/08/2022 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/08/2022 | Residential Building | REQUIRES RESUBMIT | Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. The space between roof insulation and ceiling may not be vented. Delete the Attic Ventilation Calcs. Show dryer vent size and location for venting to exterior, M1501. |