Permit Number: T22CM08046
Parcel: 13355231B

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - T22CM08046
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2022 Commercial Plumbing APPROVED Water review
11/03/2022 Fire New Construction APPROVED
11/02/2022 Site Zoning APPROVED
11/29/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
11/02/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM08046

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. 2018 IBC - 1603.1.5. Revise plans to include missing seismic information, whether or not the LFRS governs the design.
2. 2018 IBC - 1704.3. Provide a statement of special inspections, to include all information provided in this section.


BUILDING REVIEW COMMENTS:
Denied
1. 2018 IBC - 107.2.6. Provide a site plan as described in this code section.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Denied
1. 2018 IBC - 102.7.1. Provide electrical plans. The plans indicate that electrical work will take place (eg. footing details on pg 3001 show electrical conduit by others) but no electrical plans have been provided.


PLUMBING REVIEW COMMENTS:
Denied
1. 2018 IPC - 1101.2. Revise the plans to indicate how rain water will be drained away from the structure and to an approved location.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
10/31/2022 Site Engineering REQUIRES RESUBMIT per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at: https://tdc-online.tucsonaz.gov/#/home, the application can be found under the sub-permits section of this permit.

Scott Haseman