Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - T22CM08029
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/29/2022 | Commercial Mechanical | APPROVED | |||
| 10/31/2022 | Site Engineering | APPROVED | |||
| 11/01/2022 | Site Zoning | APPROVED | |||
| 11/29/2022 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/07/2022 | Commercial Electrical | REQUIRES RESUBMIT | Provide power for the2 new EXIT fixtures in the new area. 2018 IBC section 1008. Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC 2018 IECC, |
||
| 11/29/2022 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Provide plumbing plans and fixture specifications to show how the restroom will be modified to be ADA-compliant. Reference: Section 107.2.1, IBC 2018. 2. Show how the natural gas distribution system will be modified or verify that the existing system can accommodate the new gas-fired water heater. Reference: Section 107.2.1, IBC 2018. |
||
| 11/02/2022 | External Reviewers - Willdan | REQUIRES RESUBMIT | Activity Number: T22CM08029 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. DENIED: Provide Reflected ceiling plan: Demo and New. IBC 107.2.1 Provide construction details for window fill-in, new walls, any additional/new construction such as new header(s)? Please further clarify scope of work here. 2018 IBC 107.2.1 [Ver. 2] [Edited By david tallman] Provide complete details, cut-sheets, manner of installation and attachment (how they attach, connect and stay in place). Iwill need flame spread and smoke index rating/info for these. These are over 6' high & also require structural engineering calculations by a current AZ engineer/registrant. 2018 IBC 1607.15, Sec 803 (Please review limitations for non-fixed items under section 105.) [Ver. 2] [Edited By david tallman] Include ALL seating in occupancy load calculations & include a cueing area calc as well. How is this 'Retail'? Please include as waiting or seating area. IBC 107.2.1, Chapter 3, & section 1004. *Note that once occupancy exceeds 50 both signage and minimum 2 exits will be required. (this should be easy to meet but will affect these areas and exiting/exit lights,etc. as well.) Does this tenant space communicate with an adjoining tenant space? Please provide/show adjoining tenant space, what is that occupancy, same business, etc.? Confusing. IBC 107.2.1 Provide all ADA Detail drawings for ADA bathroom compliance-include on plans. Provide whether other changes will be made such as construction, walls, ADA backing, FRP/finish materials, etc. 2010 ADA, 2018 IBC 107.2.1 [Ver. 2] [Edited By david tallman] Is 5 ton unit existing or new? Please confirm/verify (if new, then weight, eng calcs, const, more info required.) [Ver. 2] [Edited By david tallman] If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
| 11/28/2022 | Fire New Construction | REQUIRES RESUBMIT | Resolve building comments |