Permit Number: T22CM08013
Parcel: 135083840

Address:
7338 E JUAREZ ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - T22CM08013
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/23/2023 Zoning Modifications - DDO PENDING ASSIGNMENT
03/21/2023 Residential Building REQUIRES RESUBMIT T22CM08013

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet Zoning and other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Indicate the location and size of the water line from property line (meter) to building, R106.1.1. Show an existing or upgraded 1” line to the water heater. Minimum size for a pipe supplying two bathrooms within the building is 1”, P2903.7.

FLOOR PLANS:

1. Show sleeping rooms with R310 compliant egress. Add a master bedroom window/door to exterior or show existing location.

STRUCTURAL PLANS:

1. Show a beam size with appropriate load carrying capacity, R301.1. The (2) 2x8 beams shown at two locations at the east patio cover are undersized.

SECTIONS - DETAILS:

1. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5). Update detil #3 sheet A3.
2. Show roof (uplift resistance) fasteners (H2.5) with appropriate uplift capacity, R802.11 amended.
3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF. Update detail #6 sheet A3.

ELECTRICAL PLANS:

1. Interior alterations require the installation of smoke alarms at existing bedrooms, R314.2.2. Provide notation if the smoke alarms are existing or proposed.
2. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6.
3. Show one 20 AMP branch circuit in the laundry area; this circuit may not serve other locations, E3703.3 and 3901.8.
4. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Adjustable security light fixtures are unshielded, not FCO.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
03/23/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM08013
Addition
7338 E JUAREZ ST Zoning R-1

TRANSMITTAL DATE: March 23, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: The minimum required front street perimeter yard is 20 feet or one and one-half the height of the proposed wall (H), measured from the street property line , whichever is greater, up to a maximum of 90 feet. Based on a wall height of 7’-4” the required street perimeter yard setback from the proposed carport structure to the north property line is 20’-0”, the proposed setback is 18’-3”. A Design Development Option (DDO) will need to be processed and approved to reduce the setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.

2.COMMENT: Based on the subdivision plat map it appear that the property line distances are incorrect provided below is the plat map.
https://www.tucsonaz.gov/apps/maps-and-records/subdivisions/details/MP-16029&


If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov