Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/12/2022 | Commercial Electrical | REQUIRES RESUBMIT | Provide a grounding detail for the Electrical Service. Provide Available fault Current calculations and AIC ratings for all the service equipment and Panel. Provide fuse types in the service disconnect. Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC 2018 IECC, City of Tucson Commercial Plan /Permit Submittal Requirements. |
||