Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/21/2022 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/21/2022 | Commercial Plumbing | REQUIRES RESUBMIT | The latest sketch needs to supply some more information and show that the pipe and fittings will be installed per code so I can approve the drawing. • What are the fixtures connected to each branch? • Which traps are located above the slab? • Where are the cleanouts located? • What is the length of the standpipe for the clothes washer? • Is the dirty arm for the clothes washer connecting to the 3” common vent above or below the other trap? • Are you hot and cold supplying water to each fixture? • Do the water connections to the clothes washer have water hammer arrestors? • Is the hot water supplied by a new water heater? If so, show how the water heater will be installed (e.g. valves, expansion tank, T&P relief, insulation, etc.). |