Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - T22CM08005
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/07/2022 | Commercial Electrical | APPROVED | |||
11/29/2022 | Commercial Mechanical | APPROVED | |||
11/29/2022 | Commercial Plumbing | APPROVED | |||
10/28/2022 | Site Engineering | APPROVED | |||
11/01/2022 | Site Zoning | APPROVED | |||
12/01/2022 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/02/2022 | External Reviewers - Willdan | REQUIRES RESUBMIT | Activity Number: T22CM08005 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. DENIED: Please provide sealed structural engineering analysis for RTU being added (750#) 2018 IBC 107.2.1. Please provide roof opening detail and any additional required framing/support per engineer for RTU being installed. Please provide further information/explanation as to the use of the TI space-what kind of 'Studio'? Too vague, please advise. 2018 IBC Sec 107.2.1 & 304. [Ver. 2] [Edited By david tallman] If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
12/01/2022 | Fire New Construction | REVIEW COMPLETED |