Permit Number: T22CM08005
Parcel: 117060640

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM08005
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2022 Commercial Electrical APPROVED
11/29/2022 Commercial Mechanical APPROVED
11/29/2022 Commercial Plumbing APPROVED
10/28/2022 Site Engineering APPROVED
11/01/2022 Site Zoning APPROVED
12/01/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
11/02/2022 External Reviewers - Willdan REQUIRES RESUBMIT Activity Number: T22CM08005

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


DENIED:
Please provide sealed structural engineering analysis for RTU being added (750#) 2018 IBC 107.2.1.
Please provide roof opening detail and any additional required framing/support per engineer for RTU being installed.
Please provide further information/explanation as to the use of the TI space-what kind of 'Studio'? Too vague, please advise. 2018 IBC Sec 107.2.1 & 304. [Ver. 2] [Edited By david tallman]


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/01/2022 Fire New Construction REVIEW COMPLETED