Permit Review Detail
Review Status: In Review
Review Details: RESIDENTIAL NEW DWELLING v.2
Permit Number - T22CM08000
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: In Review
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/12/2022 | Site Zoning | APPROVED | |||
| 12/14/2022 | NPPO | NOT REQUIRED | |||
| 12/21/2022 | Site Engineering | NOT REQUIRED | |||
| 01/20/2023 | Bldg Permits - Post Review Express | REQUIRES RESUBMIT | Residential comments require attention. | ||
| 01/05/2023 | Residential Building | REQUIRES RESUBMIT | T22CM08000 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet Zoning and other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans. Provide a clear and concise construction plan set. Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits SITE PLAN: 1. Show the location and size of the building water and sewer lines from property line to the building, R106.1.1. Identify the utility lines requiring upgrade or replacement. SECTIONS - DETAILS: 1. Show a cross-section detail for the new exterior walls, R106.1.1. Show the minimum 12” footing depth below the undisturbed ground surface with 12” minimum width for wood framed walls with minimum of one #4 rebar in the proposed continuous footing, R403.1. 2. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5) with minimum ½” diameter anchor bolt and treated sill plates, R602.10.8 & R403.1.6. This may require a concrete stem when the floor is less than 6” above grade. PLUMBING PLANS: 1. Show an individual accessible water supply shut off for each dwelling unit, P2903.9.1. 2. Clarify the pipe diameter at the point of connection of the new cold water line to existing service pipes. Existing water pipes may require replacement with larger sizes for controlling excessive water flow rates, P2903.7. A minimum 3/4” pipe is required for supplying water to the new bathroom group fixtures. 3. Show the location of the bathroom branch drainpipe connection to the existing building drain, Table P3005.4.1. If you have any questions, please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review Submit a corrected plan set at https://www.tucsonaz.gov/pdsd |
||
| 12/09/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |