Permit Number: T22CM07950
Parcel: 11504520B

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - T22CM07950
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2023 Bldg Permits - Post Review REVIEW COMPLETED
08/25/2023 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 8/21/2023 1:29:31 PM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall
not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 8/16/2023 10:25:08 AM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 8/24/2023 8:35:00 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 8/17/2023 5:26:57 PM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 8/20/2023 10:07:08 PM
Plumbing Revision Sink Relocation = OK subject to field inspection
•Coffee water connection will need an ASSE 1024 Backflow -IPC 608.17.1.2 ,Subject to field inspections
•SK-1 sink selection not detailed, will need to meet IPC section 303, Subject to field inspections
08/23/2023 PDSD Application Completeness REVIEW COMPLETED