Permit Number: T22CM07950
Parcel: 11504520B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM07950
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2022 Commercial Plumbing APPROVED Water review
11/02/2022 Site Zoning APPROVED
10/31/2022 Site Engineering NOT REQUIRED
11/29/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
11/02/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM07950

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
Denied
1. The occupant load factor used for the fitness area is not corrected. Provide a corrected occupant load calculation in accordance with Table 1004.5
2. The fixed seating for the assembly areas have not been calculated properly. Provide a corrected occupant load calculation in accordance with Section 1004.6.
3. The egress corridor wall type doesn't appear to be rated properly. The egress corridor must meet the same rating as the interior exit stairway shaft. Provide clarification and provide a correctly rated wall.
4. Door #128 doesn't appear to be rated properly. This door is in located in a rated assembly. Provide a properly rated door in accordance with Section 716.


MECHANICAL REVIEW COMMENTS:
Denied
Provide mechanical plans including ventilation calculations (IMC2018,106.3.1)


ELECTRICAL REVIEW COMMENTS
Denied
No electrical submitted for review. Cannot approve electrical permit.


PLUMBING REVIEW COMMENTS:
Denied
1). A3-80 & B-65 occupancy types & loads shown on plan page G1.01 require 2 mens toilets, 2 mens Lavs, 2 womens toilets, 2 womens lavs, High/low drinking fountain, & a service sink. Update all affected pages & include plumbing plans -IPC 403.1
2). Does the coffee area on plan page A2.01 need water supply and drain? if yes add plumbing plans -IPC 106.3.1
3). G0.01 general notes refer to plumbing drawings, plumbing drawings not sent. -IPC 106.3.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/29/2022 Fire New Construction REQUIRES RESUBMIT