Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - T22CM07931
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/05/2023 | External Reviewers - SAFEBuilt | APPROVED | Activity Number: T22CM07931 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: APPROVED BUILDING REVIEW COMMENTS: CONDITIONALLY APPROVED Conditionally approved, per the following: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel, or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The registered design professional is responsible for following ALL applicable Federal, State, and local Municipal Codes and Ordinances. MECHANICAL REVIEW COMMENTS: CONDITIONALLY APPROVED Conditionally approved, per the following: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel, or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The registered design professional is responsible for following ALL applicable Federal, State, and local Municipal Codes and Ordinances. ELECTRICAL REVIEW COMMENTS APPROVED PLUMBING REVIEW COMMENTS: APPROVED If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
01/18/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/18/2023 | Fire New Construction | REQUIRES RESUBMIT | Comment: You shall provide a written narrative letter of the operations in every area of the building all throughout and storage quantities. Provide a full Hazardous Material Inventory Statement (HMIS) Per IFC 2018, Chapter 50, Section 5001.5.2. Provide MSDS and all quantities of chemicals being used throughout the buildings and define the operations in those areas. Provide a Hazardous Material Management plan per the IFC 2018, Chapter 50 Section 5001.5.1 Add notes to the drawings: Owner shall obtain an operational permit from TFD for flammable liquids with a site plan showing the storage of the materials. Provide information regarding the required alarm for extraction and if the building has a fire alarm system shall be connected. Questions: Jennifer Peel-Davis Tucson Fire Department Fire Plans Examiner Fire Inspector I, II and Fire Alarm Plans Examiner Jennifer.Peel-Davis@Tucsonaz.gov Desk: 520-837-7033 |
||
12/19/2022 | PDSD Application Completeness | REVIEW COMPLETED |