Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - T22CM07931
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/26/2023 | Water Sterilization Report (Deferred Submittal) | APPROVED | |||
05/26/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/26/2023 | Air Balancing/Commissioning Report (Deferred Submittal) | REQUIRES RESUBMIT | The total air flow rates for RTU-1 and RTU-3 are more than 10% below the design values and RTU-6 has been deleted. Provide acceptance of the air balance from the engineer of record. |