Permit Number: T22CM07931
Parcel: 14042002A

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - T22CM07931
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2023 Water Sterilization Report (Deferred Submittal) APPROVED
05/26/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/26/2023 Air Balancing/Commissioning Report (Deferred Submittal) REQUIRES RESUBMIT The total air flow rates for RTU-1 and RTU-3 are more than 10% below the design values and RTU-6 has been deleted. Provide acceptance of the air balance from the engineer of record.