Permit Number: T22CM07919
Parcel: 127101450

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - T22CM07919
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/01/2023 Zoning Modifications - DDO PENDING ASSIGNMENT
03/14/2023 Residential Building REQUIRES RESUBMIT T22CM07919 R1

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance.

Provide a clear and concise construction plan set. Sample drawings are shown as an example: https://www.tucsonaz.gov/pdsd/residential-permits

SITE PLAN:

1. Indicate the location utility lines supporting the alterations, R106.1.1. Show the electrical panel and location of sewer line connection.

FLOOR PLANS:

1 Clarify the usage of the proposed enclosed garage and addition, R106.1.1. Bedrooms require compliant egress to the exterior.
2 An opening from a garage directly into a sleeping room is not permitted, R302.5.1.
3 Show the dimensions and fixture layout of the bathroom, Figure R307.1.

STRUCTURAL PLANS:

1. Provide a Roof Framing Plan showing the location and size of beams, headers, and rafters for supporting live and dead structural loads, R804.

SECTIONS - DETAILS:

1 Show a cross-section detail of the proposed exterior wall, R106.1.1. Show 3/8” structural or ½” non-structural wall sheathing of the proposed exterior wall, R106.1.1. Include the R-30 ceiling and R=13 wall insulation placement, N1102.1.
2 Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” x 12” continuous #4 rebar reinforced footing, R403.1. Show with dimensions the exterior wood siding, insulation, interior sheathing, and pressure treated sill anchored with ½” x 10” bolts. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5.
3 The framed wall may require a concrete stem for achieving the 6” clearance between framing and ground (R317.1 item 5).

MECHANICAL PLANS:

1. Provide a plan showing the location of the heating/cooling equipment such as a Mini-split.

ELECTRICAL PLANS:

1. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, E3404.12.
2. Provide an electrical plan showing the receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
3. Show at least one wall switch controlled light at outdoor entrances or exits and all habitable rooms, E3903.3.
4. Notate the protection of new or extended interior 15A & 20A circuits with combination type arc-fault circuit interrupters, E3902.16.

If you have any questions, please contact:
Ken Van Karsen
(520) 791-5550
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
03/21/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM07919
Addition
6229 E ROSEWOOD ST Zoning R-1

TRANSMITTAL DATE: March 21, 2023

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This comment is still applicable please provide property line distances. In the link provided below is the plat map with the distance for the lot. : https://www.tucsonaz.gov/apps/maps-and-records/subdivisions/details/MP-10004&
The East and west property line distance is 102.70

1.COMMENT: Provide a Residential Plot Plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf This shall in include:

d. Property line distances




This comment is still applicable.
2.COMMENT: Provide a floor plan for the existing residence on the plan so that Zoning can verify if the requirements of UDC Article 4.9.7.B.7 are applicable to this project.





If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov