Permit Number: T22CM07891
Parcel: 12909146C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM07891
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2022 Commercial Electrical APPROVED
11/28/2022 Commercial Mechanical APPROVED
11/28/2022 Commercial Plumbing APPROVED
10/28/2022 Site Engineering APPROVED
10/31/2022 Site Zoning APPROVED
11/28/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
11/02/2022 External Reviewers - Willdan REQUIRES RESUBMIT Activity Number: T22CM07891

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


DENIED:
Sheet A0.0 Existing Accessible restrooms are subject to a Favorable Field Inspection. Existing Drinking Fountain is subject to inspection to verify High Low is provided.
Sheet A1.0 Training room requires 2 exits based onOccupant Load. Per IBC Table 1006.2.1
Sheet A1.0 Provide accessible path of travel to Accessible Restroom, Parking and Public Way. Per IBC Chapter 11 and ICC A117.
Sheet A3.0 Provide 12 GA Hanger wire at each runner or cross runner maximum 8" from the wall.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/26/2022 Fire New Construction REVIEW COMPLETED