Permit Number: T22CM07869
Parcel: 14029003H

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - T22CM07869
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2022 Fire New Construction APPROVED
11/03/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/01/2022 External Reviewers - Willdan REQUIRES RESUBMIT Activity Number: T22CM07869

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


DENIED:
PLEASE PROVIDE A SCOPE OF WORK
PROVIDE SPECIAL INSPECTION CERTS. FOR LISTED SPECIAL INSPECTIONS IF E.O.R. IS NOT DOING INSPECTIONS. IBC 1704.2
KEYNOTE #11 IS NOT LISTED.
KEYNOTE #8 IS WRONG REFERENCE.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
10/31/2022 Site Engineering REQUIRES RESUBMIT Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at: https://tdc-online.tucsonaz.gov/#/home, the application can be found under the sub-permits section of this permit.
Scott Haseman
scott.haseman@tucsonaz.gov
10/31/2022 Site Zoning REQUIRES RESUBMIT FROM: Samuel Rogers
PDSD Zoning Review Section

PROJECT: T22CM07869
Truck Dock Infil - 1st Review
3440 E BRITANNIA DR Unit:150

TRANSMITTAL DATE: 10/31/2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: All exterior work proposed on commercial sites must be approved on a Development Package prior to the building permit’s approval. For development package info see: https://www.tucsonaz.gov/pdsd/apply-permit#Development%20Package


02. COMMENT: Additional comments may be applicable once the development package is issued.


If you have any questions about this transmittal, Contact Samuel Rogers at Samuel.Rogers@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans