Permit Number: T22CM07850
Parcel: 137055290

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - T22CM07850
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
12/13/2022 Commercial Mechanical REQUIRES RESUBMIT 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. The heating/cooling load calculations show two different roofs: 800 square feet that has R-11insulation and 800 square feet that has 3” of insulation on a steel deck. Is this the actual situation, with 1600 square feet of total roof area? Reference: Section C403.1.1, IECC 2018.
3. Show how the existing HVAC system offsets part of the total calculated heating/cooling load. Reference: Section 107.2.1, IBC 2018.
4. Show the size, routing, and termination of the condensate drain. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.