Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - T22CM07847
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/28/2022 | Site Engineering | APPROVED | |||
10/31/2022 | Site Zoning | APPROVED | |||
11/30/2022 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/03/2022 | Commercial Electrical | REQUIRES RESUBMIT | Please provide complete compliance with the 2018 IECC for the lighting. ComCheck is acceptable. | ||
11/28/2022 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Condensate drains shall be terminated at an approved disposal location (i.e. not a splash block on the roof). Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson. 2. HVAC General Note #7 refers to detail #3 on sheet M2 but sheet M2 is not part of the drawing set. Reference: Section 107.2.1, IBC 2018. 3. The outside air calculations should be noted as being based on the 2018 IMC. Reference: Section 107.2.1, IBC 2018. |
||
11/28/2022 | Commercial Plumbing | REQUIRES RESUBMIT | |||
11/02/2022 | External Reviewers - Willdan | REQUIRES RESUBMIT | Activity Number: T22CM07847 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. DENIED: Sheet T1 Provide a site plan showing accessible path of travel to the front entrance and to the public way. IBC Chapter 11 And ADAAG. Sheet T1 I did not find the list of materials in the submittal package. Sheet S1 Hilti Kwik Anchors and Titen HD Screw Anchors require special inspection per ESR and Chapter 17 Sheet S2 Special inspection required for welding and for Hilti Bolts per IBC Chapter 17 Sheet A4 Show locations of roof drains and over flow scuppers. If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
11/30/2022 | Fire New Construction | REVIEW COMPLETED |